ABB 3BDH001010R0005ABB 3BDH001010R0005 (CI930F PROFIBUS DP Redundant Master Communication Module)
ABB CI930F PROFIBUS DP Redundant Master Communication Interface Module, Order Article No. 3BDH001010R0005, Freelance AC 900F DCS Dual Line Redundancy Fieldbus Master Card Core Function Description This is the latest hardware revision of the CI930F series, exclusively engineered for ABB Freelance AC 900F distributed control systems as a hot-swappable PROFIBUS DP master with native dual-line bus redundancy (Line A / Line B) for fault-tolerant industrial field communication. It acts as the bridge between AC900F CPU controllers and PROFIBUS DP slave field devices, supporting DP-V0 cyclic real-time I/O data exchange and DP-V1 acyclic parameter diagnostic access. Core Function Description This is the latest hardware revision of the CI930F series, exclusively engineered for ABB Freelance AC 900F

Product Description
ABB CI930F PROFIBUS DP Redundant Master Communication Interface Module, Order Article No. 3BDH001010R0005, Freelance AC 900F DCS Dual Line Redundancy Fieldbus Master Card Core Function Description This is the latest hardware revision of the CI930F series, exclusively engineered for ABB Freelance AC 900F distributed control systems as a hot-swappable PROFIBUS DP master with native dual-line bus redundancy (Line A / Line B) for fault-tolerant industrial field communication. It acts as the bridge between AC900F CPU controllers and PROFIBUS DP slave field devices, supporting DP-V0 cyclic real-time I/O data exchange and DP-V1 acyclic parameter diagnostic access. Core Function Description This is the latest hardware revision of the CI930F series, exclusively engineered for ABB Freelance AC 900F
Technical Specifications
| Brand | ABB |
|---|---|
| Model | 3BDH001010R0005 |
| Category | Industrial Automation |
| rt | ABB 3BDH001010R0005 (CI930F PROFIBUS DP Redundant Master Communication Module) |
| Symptom | New CI930F fails to activate after live insertion mid-process operation. Root cause: Mismatched firmware revision between spare module and running AC900F CPU program. Fix: Download matching firmware to spare module offline before executing hot-swap maintenance procedure. |
| Connector | 9-pin D |
| Mounting | Rack Mount |
| Speed | 9.6 kbps |
| Speed 2 | 6 Mbps |
| Redundancy | DP Redundant |
| Redundancy 2 | dual-port redundant |
| Origin | Germany / Original |
| Condition | New Original Factory Sealed |
| Warranty | 12 Months |
| Shipping | Global Delivery via DHL/FedEx/UPS |